5C Segregation of Category 4 Circuits and Circuits of Other Categories (5C 第4類電路與其他類別電路的分隔)
“第4類電路”(category 4 circuit) 指高壓電路。
6I Protection Requirement of High Voltage Circuit (6I 高壓電路的保護要求)
應根據生產商的資料設定高壓裝置的保護器件,並需妥善設計以確保故障消除時間在器具的額定值範圍內。
8A (7) 11kV and 22kV Main Switch (11千伏及22千伏總開關掣)
11kV Main Switch:Circuit Breaker - rated for use at 11kV and fault level of 18.4kA rms for 3 seconds,lightning impulse withstand voltage should not be less than 75kV peak.
22kV Main Cwitch:Circuit Breaker - rated for use at 11kV and fault level of 25kA rms for 3 seconds,lightning impulse withstand voltage should not be less than 125kV peak.
Main Breaker - normally be of draw-out type and lockable at that position
斷路器、接地開關及隔離器之間須設有連鎖設施。
開關設備的插座必須設有安全活門( Safety shutter)。
接地開關(Earthing Switch):fault making type,operated by mechanical means when it is closed to circuit earth position
17A Warning Notice for Substations and Switchrooms (17A 電力分站及開關掣房的警告性告示)