2022/04/09

【數據中心設計】CDCP 學習筆記 - 數據中心 (Part 3-1) - Data Centre Design - Locations, Building and Construction

數據中心選擇合適的地點不僅需要考慮到新數據中心的技術要求,而且還涉及到從商業角度的許多方面。然而,現實中,業主所做出的選擇,往往更看重地址的商業和營銷方面。因此,這可能會導致地點選擇上對於技術評估方面的規定和要求過多。

位於香港新界西貢區將軍澳的高端數據中心MEGA Plus


Site selection criteria

• Site selection is difficult

  • - Technical requirements evaluation(技術方面考量)
  • - Decision making process/business evaluation(商業方面考量)

• Technical evaluation

  • - Often done by engineers
  • - Want the best to meet design criteria

• Business evaluation

  • - Done by senior management
  • - Return On Investment (ROI) / cost
  • - Prestige
  • - Location

• Proper planning, analysis and studies must be performed to avoid impact after the data centre construction on:

  • - High-availability
  • - Reliability
  • - Manageability
  • - Scalability
  • - Cost of operations
  • - Non-compliance to standards

• Select sites that cater for current needs and future (planned) growth and business requirements(時刻考慮將來的需要)


Location evaluation

• Potential natural hazards

  • - Lightning, flooding, typhoons
  • - Forest fires
  • - Seismic activity (earthquake)

• Potential man-made hazards

  • - Flight path(不要建在離機場跑道較近的地方)
  • - Tunnels, lakes(不要建在隧道上方,水域附近的地方)
  • - Train station/airport (Train station的震動關係)
  • - RF towers(Electromagnetic signal interference)
  • - Power distribution network(Electromagnetic fields)
  • - Industrial pollution(air contamination)

• Proximity evaluation to emergency services / first responders

  • - Fire, police, medical facilities(不要太接近這些設施)

• Proximity to the neighbourhood (urban/industrial)(不要太接近居民區:backup generator的噪音;不要太接近工業區:空氣污染)

• Proximity to public transport and public roads(交通儘量便利)

• Proximity to 'high risk' targets(避免靠近以下地點)

  • - Embassies
  • - Government buildings
  • - Power stations
  • - Radio/TV stations

• Convenience should not overrule security!


Building evaluation

• Building evaluations;

  • - Rent / Buy / Build
  • - History of the building and/or area (是否以前有過flood, fire etc.)
  • - Building codes(加改建有無要求)
  • - Level/floor within the building(儘量不要在首層Ground Floor和頂層Top Floor)
  • - Space required for each functional area incl. potential expansion(server room space? UPS room space?)
  • - Security
  • - Glass windows/panels(儘量不要用玻璃幕牆,不如混凝土牆堅固)
  • - Floor loading(IT設備越來越重, loading requirement)
  • - Slab to slab height(有無條件加raised floor,天花是否夠headroom走線)
  • - Power capabilities(Redundancy and capacity)
  • - Network capabilities(Redundancy and diversity)(Diversity更重要,儘量選擇多於一家網絡設備供應商)
  • - External supply capabilities(Re-fueling of standby generator tanks / Delivery of heavy/big equipment and route to the data centre)(設備運輸問題, loading for delivery route)

• Budget to build / budget to run(技術始終要受到預算的限制)


香港的數據中心

在香港,設置數據中心的選址途徑有多種,包括:

  • 改裝現有工業大廈
  • 在政府售賣的未發展之土地上設置
  • 在公開市場購買或租用土地/樓面空間

有關香港數據中心選址的詳細介紹可參考:Link


改裝現有工業大廈

本港許多現有的工業大廈,樓底高、樓面負荷量大和樓層間隔具彈性,可改裝成為數據中心。視乎所需空間,數據中心可佔用部分或全幢工業大廈。

在香港,大型數據中心多匯聚於荃灣、葵涌、沙田、觀塘、九龍灣、新蒲崗、柴灣及將軍澳等地區。

工業大廈位處地段的土地契約上包含土地使用及其他方面的限制。位於「工業」、「商業」或「其他指定用途」註明「商貿」地帶的工廈業主可申請將合資格工業大廈的一部分改為數據中心用途,並免繳豁免書費用。興趣在工業大廈設置數據中心的人士應查閱地契是否已准許作數據中心用途。若否,業主可申請修訂土地契約或臨時豁免書。