2022/04/30

【數據中心設計】CDCP 學習筆記 - 數據中心 (Part 6-3) - Data Centre Design - Power Infrastructure

Grounding in the data centre 數據中心接地系統

主要作用:

  • Establish voltage reference
  • Clear electrical faults
  • Provide RF/ESD discharge path (SRG)
  • Carry lightning currents

接地阻值 < 1 Ohm,要求所有金屬物體都要接地,包括:機櫃,UPS,架高地板


Common Mode Noise (CMN) 

  • The voltage between neutral and ground
  • 要求:
    • Preference < 1 Volt
    • Acceptable up to 1% of line/phase to neutral voltage
    • The general recommendation by vendors < 3 Volt
  • 電纜越長,諧波越多,相位不平衡會增加CMN


Location of the isolation transformer? 隔離變壓器放哪裡?


  • Iso-Tx: delta-wye type 
  • Should be as close to the ICT equipment as possible
  • PDUs with built-in isolation transformer provides the best performance
  • Filtering of power disturbances
  • Reduction of Common Mode Noise (CMN)
  • K-13 type Tx is the most common type for data centres
  • In computer rooms with high harmonic content, one might want to consider upgrading the neutral to double size.


Forms of Distribution boards 配電櫃/箱的間隔

  • Form 1 - No separation
  • Form 2 - Separation of busbars from other functional units
  • Form 3 - Separation of busbars from all functional units and between all functional components but not their terminations
  • Form 4 - Separation of busbars from all functional units and between all functional components including their terminations

詳細分類可參考之前文章:【低壓制櫃設計】低壓制櫃的間隔和形式(Segregation & Form of LV Switchboard)


IP (Ingress Protection) grades 防塵防水等級

  • Most commonly found are IP20 / IP21 for UPS and other electrical systems in the data centre.
  • Selecting the digit 1 is sometimes useful as the UPS systems may be located in an area where overhead air conditioners are being applied. (一般情況UPS都為IP20)


Power quality: guidelines 電能質量要求

主要考慮參數:

  • Voltage: Nominal +/- 10% (EMSD要求voltage drop不可以超過 4%)
  • Frequency: Nominal +/- 10%
  • Common Mode Noise: < 1% of Phase to Neutral
  • Total Harmonics Distortion of Voltage (THDv): < 8% (non-linear load)
  • Total Harmonics Distortion of Current (THDi): < 12%


CBEMA / ITI(C) curves

  • CBEMA - Computer and Business Equipment Manufacturers Association
  • ITI(C) - Information Technology Industry Council
  • The CBEMA (ITI or ITIC) curve indicates what voltage levels are acceptable for ICT equipment. All manufacturers comply with the CBEMA curve.

  • 黃色高光區域:設備正常運行
  • 右上Prohibited Region:設備可能損壞
  • 右下No Damage Region:設備不會損壞,但亦不會運行


Label power versus actual power consumption(標籤上的功率 vs 實際使用功率)

  • Real power usage is typically 20-40% less than the label/plate power
  • based on the actual hardware configuration and other factors such as CPU load etc


Sizing power usage for the data centre (數據中心的電力需求估算)

Average Watt/Floor Area (sqm) - Power Density

  • Low-density data centre: 500 W/sqm
  • Medium-density data centre: 1,000-1,500 W/sqm
  • High-density data centre: 2,000-2,500 W/sqm
  • Extreme-density data centre: > 3,000 W/sqm

Rack Usage Power - Rack Power

  • Standard racks: 1-3 kW
  • Mixed racks: 5-8 kW
  • Blade servers: > 15 kW (as high as 28 kW per rack)
  • Add non-standard size equipment
    • Mainframes, storage, etc


  • UPS power: Add 35% to cater for a buffer.
  • Lighting power: can also refer to the Building Energy Code requirement to estimate
  • Cooling power: UPS power x 1.2 for refrigerant-based systems / UPS power x 1 for chilled water based cooling.
  • Safety factor: 20 ~ 25%


Sizing power usage for Generator-Set(後備發電機的電力需求估算)

主要考慮因素:

  • 實際後備負載需求:kVA/kW requirement of the installation attached
  • 設備啟動時的衝擊電流:Expected Inrush currents on the generator during operations
  • Harmonics returning from the connected installation


沒有留言:

發佈留言

任何人若留有政治言論,個別使用者將會被隔離這個網誌,留言系統或將會被限制,甚至關閉