Water supply in a Data Centre
- Fire suppression
- Sanitary facilities
- Makeup water for cooling
- Cleaning
- General facilities maintenance (gardens etc.)
Backup water supply: Water storage tanks
- for the fire suppression installation
- for makeup water for cooling towers
- for chilled water backup (buffer storage)
- for off-peak chilled water storage (thermal storage)
Backup water supply: Well water / Retention pond
Well water
- Cleanliness
- Supply capability
- Drilling could be very expensive
Retention pond
- Fixed quantity
- Large area required
- Water temperature varies
- Water quality checks on a regular basis
Fire protection and safety
- originate from electrical sources
- Equipment (overheating, zinc whiskers or dead shorts)
- Electrical distribution (wiring, loose connections, sparks)
- Light fixtures
- Bad connections, overloading and dust are contributing factors
- During various data centre audits it is proven that a high percentage of data centres have (potential) issues with fire protection
Requirements for Data Centre fire suppression
- Detect as early as possible
- Safe for humans (as much as possible)
- Environmentally friendly
- Effective for fires in the data centre and supporting facilities
- Do not, or minimize, damage to sensitive equipment
- Comply with national and building code
Standards
- NFPA 75 / NFPA 72
- NFPA 2001 / ISO 14520
- Local codes
Detection systems
- VESDA (Very Early Smoke Detection Apparatus)
- HSSD (Highly Sensitive Smoke Detection)
- Works via air sampling
- 1000 times more sensitive than standard smoke detectors
- Care must be taken, especially during building works such as hacking, drilling, etc.
Smoke detectors for fire panels
- Ionization detectors(較Photoelectric detector更靈敏)
- Uses low radiation (harmless) material (americium-241)
- When smoke enters the detector the ions create an electrical path setting alarm condition
- Photoelectric detector
- Uses a light source (i.e. LED etc.) and photocell
- When smoke enters, deflection of light will activate photocell triggering an alarm
- Sprinklers act as detection and activation
- Slow, typically activates at 70 degrees or higher
- accidental damage will result in immediate water problems
- Concealed sprinkler systems
- More attractive finish / Less risk of damage
- The cover plate drops off at 57 Celsius and the deflector drops down
- Sprinkler head activates at 70 Celsius or higher
Wet / Dry sprinkler system 考慮因素
- Preferred to have dry pipe principle (pre-action)
- Not harmful to humans
- Environmentally friendly
- Effective
- Leaves water damage —— Drainage piping
- Slow response
- Widely used in data centres as a secondary system
- Compulsory under most building codes for high-rise buildings
Fire suppression systems:
- Halon 1301 —— banned in most countries, depletes the ozone layer
- Carbon Dioxide —— lowest-priced, not allowed in most countries in occupied areas
- FM200 —— widely used in data centres, harmful gas will develop when FM200 is burned
- Novec —— cost-effective, clear gas, environmentally safe, cylinders need to be close to the hazard area, containers can be refilled on site
- Inergen —— more appropriate for the larger computer rooms, 10 times more space compared to FM200
- Argonite —— reduces oxygen levels down to approx. 12.5%, loud noise generated
- FE13 —— allows high nozzles (up to 8 metres, other 4 metres)
- Pyrogen —— 氣溶膠滅火劑, no piping and no pressure cylinders required
Best practices for main fire suppression
- Install VESDA/HSSD type of system
- Use any of the gas-based systems as the primary fire suppression system
- Use a pre-action sprinkler as a secondary system
- Ensure that the room is properly sealed
- Ensure that gas content is enough to achieve concentration levels required
- Create extraction vents
- Proper maintenance
理想情況下,火災當然需要被盡可能快地探測到,因此快速的反應系統,如VEDSA是最合適的。氣體滅火系統作為主要系統,對數據中心的設備幾乎沒有傷害。如果法例要求,水系統可以作為後備系統來配置。
房間需要被密封,一旦滅火氣體被釋放,氣體可以被控制在房間內。需要留意的是,滅火氣體亦有可能會從電纜盤的孔中洩漏。滅火氣體的量需要仔細計算,滅火的氣體量需要一個濃度的要求,氣體量不能過少也不能太多。
另外,需要配備抽風系統,以便在排除氣體後能夠將氣體抽出房間。
Handheld extinguishers —— Class C (for Data centres)
- Fires involving energized electrical equipment such as appliances of all kinds, motors, computers etc.
- Extinguishers contain carbon dioxide, Halon, dry chemical or liquid extinguishing agent
- Note: The indicator of classes can vary per country, class C can be indicated by class E
Signage and safety
- Exit / Emergency signs to be located at: (可以跟BS 5266設計)
- Every escape door
- In pathways leading to doors (arrows)
- Must be visible from all areas in the hazard area
- Evacuate area immediately
- Alarm bell
- Strobe light
- Gas release abort - (Telephone / Intercom)
- Gas manual release
Regulatory requirements / Best practice
- EPO (Emergency Power Off)(防止火勢擴散)
- Auto unlock doors - Doors should use the swing-out principle (code permitted)
- Escape routes should be clear and within the distance required by law
- (Automatic) the shutdown of air conditioners - Country dependent, check regulation
- Integration with existing building fire panel
- Gas manual release and gas abort buttons
- Fulfil local fire-codes
沒有留言:
發佈留言
任何人若留有政治言論,個別使用者將會被隔離這個網誌,留言系統或將會被限制,甚至關閉