2022/05/15

【數據中心設計】CDCP 學習筆記 - 數據中心 (Part 9-3) - Data Centre Design - Cooling Infrastructure

Up Flow or Down Flow

  • Up Flow
    • Can be installed with or without a raised floor
    • Limited airflow guidance (need to use ducting)
  • Down Flow
    • Can 'only' be used with raised floor
    • Allows for air flow guidance through a raised floor

Wall flow
  • A new trend is a wall-flow concept
  • CRAHs are mounted in the service corridor and are blowing the air horizontal into the data centre
  • Racks are positioned directly on the slab
  • Racks can be taller and heavier
  • Return air is ducted to the service corridor
  • No need for the raised floor

在Service Corridor上安裝CRAC unit,不需要架空地板,為了避免冷熱空氣的混合,需要確保熱空氣通過管道或者通過假天花被引回Service Corridor。


架空地板冷卻方式與非高架地板冷卻方式哪個好?

  • 關於哪種方案是最好的,沒有統一的答案,取決於以下因素:
    • ICT設備的類型
    • slab-to-slab height
    • required cooling capacity
    • flexibility
  • 架空地板並不再是一種趨勢,因為未必所有建築都考慮過有架空地板的配置。


Cooling Concepts (1) —— with Raised Floor

  • Hot- and Cold-Aisle setup
    • Racks are placed Front-to-Front and Back-to-Back
    • Cold- and Hot-Air areas are separated
    • Some hot air will still flow into the cold air areas

  • A suspended ceiling can aid in guiding the hot air back to the air-conditioner without mixing with the cold-air areas
  • Increased efficiency


  • Air conditioners should be placed perpendicular to the hot aisle
    • Allow fast hot air to return
    • Allow more evenly equalised air pressure under the raised floor


Placement of equipment in the rack 

  • With traditional downflow cooling, the bottom of the rack will be colder than the top
    • Put high heat load approx. 30 cm above raised floor and not above half the rack height
    • Higher possible if you have enough CFM


在架空地板配置中,機架底部會有更多的冷氣供應量。因此,把最高的熱負荷的設備儘量放在底部。在機架的頂部,冷氣量愈少,因此冷卻能力較低。把較低的熱負荷的設備儘量放在較高部分。


Avoid leakage and short circuit air

  • Air leakage from the floor - Use grommets
  • Air leakage within the racks (back-wash) leads to in-efficiencies - Use blanking panels


The maximum throw of the air conditioner

  • Consider the maximum throw of your air conditioner (if using perimeter cooling)
    • Typically 12 - 18m
  • Too long rooms require placement of perimeter air conditioners on both sides



Cooling Concepts (2) —— with Non-Raised Floor

In-Row cooling


  • In-row cooling can be deployed when using a non-raised floor setup
  • Cooling close to the heat load leads to good efficiencies for airflow
  • Fewer racks per sqm inside the computer room
  • In-row cooling units are
    • Direct expansion
    • Chilled water
    • Fluid cooled


Overhead duct

  • Overhead, ducted, cooling dumps cold air directly in front of the racks and extract the hot air from the back
  • Ducts have often louvres/vents to regulate CFM/CMH
  • Ducts must be well designed
    • Ensure enough air volume can be dumped and extracted at the right locations
    • Air conditioner redundancy must be taken into account
  • Do not paint the ducts as paint might splinter over time causing particulates to contaminate the room
  • Inspect and clean ducts on a regular basis


Cooling Concepts (3) —— Supplemental Cooling

High-Density Cooling: Floor mount



  • Collects cool air from underfloor
  • Increases CFMto the rack
  • Flexible, Movable
  • Neighbouring racks could have a potential cooling impact


High-Density Cooling: Hot air fans

  • Collect hot air at the point of generation
  • Route directly to CRAC
  • Snap-on retrofit
  • Variable speed: as needed
  • Flexible, movable
  • Only assist with removal of heat
  • Does not assist in increasing the cold air supply


High-Density Cooling: Overhead supplement air

  • Traditional CRAC / HVAC downflow/throw units with raised floor principle need to be extensively extended
  • Ducted return to air conditioner direct from the rack
  • Top flow rack units in addition to raised floor cooling
  • Limit 10-25 kW


High-Density Cooling: Self-contained racks

  • Fully ducted supply and return, local rack cooler
  • Collect equipment exhaust air
  • Provide cooling coils in the rack
  • Specialized rack
  • Heat removal by water or refrigerant
  • Flexible / movable
  • Fire suppression considerations
  • Limit: 18-35 kW per rack
  • Cooling principles: water/dielectric/Liquid CO2/Refrigerant


Cold Aisle vs Hot Aisle Containment?



Cold Aisle Containment

  • The cold aisle area is contained
  • Cold air only goes where it needs to be, being the air-intake of the equipment
  • Air volume required for a cold aisle can be calculated by reviewing the CFM requirements of all the equipment inside the contained area
  • Typically recommended when containment is applied to the entire room
  • It is required that proper redundancy measures are taken as very little buffer air might be available in case of an air conditioner failure
  • Slight overpressure needs to be created
    • Ideally, air pressure is measured in the cold aisle area and connected to air conditioners to regulate the CFM/ CMH output
  • Be aware that CFM / CMH is variable in most of today's equipment


Hot Aisle Containment

  • The hot aisle area is contained
  • Hot air is separated from the cold air and is guided directly back to the air conditioner or outside of the building
  • Cold air is flowing throughout the entire computer room
  • Typically recommended when only a small area needs to be contained
  • Cold air is going through the entire room 
    • Cold air should only go where it is required being the intake of the equipment
  • The whole room is now acting as a buffer area
  • Works well with in-row cooling
  • Hot aisle areas can sometimes be very hot and noisy 
    • Review local regulations for personnel working in such environments


沒有留言:

發佈留言

任何人若留有政治言論,個別使用者將會被隔離這個網誌,留言系統或將會被限制,甚至關閉