Up Flow or Down Flow
- Up Flow
- Can be installed with or without a raised floor
- Limited airflow guidance (need to use ducting)
- Down Flow
- Can 'only' be used with raised floor
- Allows for air flow guidance through a raised floor
- A new trend is a wall-flow concept
- CRAHs are mounted in the service corridor and are blowing the air horizontal into the data centre
- Racks are positioned directly on the slab
- Racks can be taller and heavier
- Return air is ducted to the service corridor
- No need for the raised floor
在Service Corridor上安裝CRAC unit,不需要架空地板,為了避免冷熱空氣的混合,需要確保熱空氣通過管道或者通過假天花被引回Service Corridor。
架空地板冷卻方式與非高架地板冷卻方式哪個好?
- 關於哪種方案是最好的,沒有統一的答案,取決於以下因素:
- ICT設備的類型
- slab-to-slab height
- required cooling capacity
- flexibility
- 架空地板並不再是一種趨勢,因為未必所有建築都考慮過有架空地板的配置。
Cooling Concepts (1) —— with Raised Floor
- Hot- and Cold-Aisle setup
- Racks are placed Front-to-Front and Back-to-Back
- Cold- and Hot-Air areas are separated
- Some hot air will still flow into the cold air areas
- A suspended ceiling can aid in guiding the hot air back to the air-conditioner without mixing with the cold-air areas
- Increased efficiency
- Air conditioners should be placed perpendicular to the hot aisle
- Allow fast hot air to return
- Allow more evenly equalised air pressure under the raised floor
Placement of equipment in the rack
- With traditional downflow cooling, the bottom of the rack will be colder than the top
- Put high heat load approx. 30 cm above raised floor and not above half the rack height
- Higher possible if you have enough CFM
在架空地板配置中,機架底部會有更多的冷氣供應量。因此,把最高的熱負荷的設備儘量放在底部。在機架的頂部,冷氣量愈少,因此冷卻能力較低。把較低的熱負荷的設備儘量放在較高部分。
Avoid leakage and short circuit air
- Air leakage from the floor - Use grommets
- Air leakage within the racks (back-wash) leads to in-efficiencies - Use blanking panels
The maximum throw of the air conditioner
- Consider the maximum throw of your air conditioner (if using perimeter cooling)
- Typically 12 - 18m
- Too long rooms require placement of perimeter air conditioners on both sides
Cooling Concepts (2) —— with Non-Raised Floor
In-Row cooling
- In-row cooling can be deployed when using a non-raised floor setup
- Cooling close to the heat load leads to good efficiencies for airflow
- Fewer racks per sqm inside the computer room
- In-row cooling units are
- Direct expansion
- Chilled water
- Fluid cooled
Overhead duct
- Overhead, ducted, cooling dumps cold air directly in front of the racks and extract the hot air from the back
- Ducts have often louvres/vents to regulate CFM/CMH
- Ducts must be well designed
- Ensure enough air volume can be dumped and extracted at the right locations
- Air conditioner redundancy must be taken into account
- Do not paint the ducts as paint might splinter over time causing particulates to contaminate the room
- Inspect and clean ducts on a regular basis
Cooling Concepts (3) —— Supplemental Cooling
High-Density Cooling: Floor mount
- Collects cool air from underfloor
- Increases CFMto the rack
- Flexible, Movable
- Neighbouring racks could have a potential cooling impact
High-Density Cooling: Hot air fans
- Collect hot air at the point of generation
- Route directly to CRAC
- Snap-on retrofit
- Variable speed: as needed
- Flexible, movable
- Only assist with removal of heat
- Does not assist in increasing the cold air supply
High-Density Cooling: Overhead supplement air
- Traditional CRAC / HVAC downflow/throw units with raised floor principle need to be extensively extended
- Ducted return to air conditioner direct from the rack
- Top flow rack units in addition to raised floor cooling
- Limit 10-25 kW
High-Density Cooling: Self-contained racks
- Fully ducted supply and return, local rack cooler
- Collect equipment exhaust air
- Provide cooling coils in the rack
- Specialized rack
- Heat removal by water or refrigerant
- Flexible / movable
- Fire suppression considerations
- Limit: 18-35 kW per rack
- Cooling principles: water/dielectric/Liquid CO2/Refrigerant
Cold Aisle vs Hot Aisle Containment?
Cold Aisle Containment
- The cold aisle area is contained
- Cold air only goes where it needs to be, being the air-intake of the equipment
- Air volume required for a cold aisle can be calculated by reviewing the CFM requirements of all the equipment inside the contained area
- Typically recommended when containment is applied to the entire room
- It is required that proper redundancy measures are taken as very little buffer air might be available in case of an air conditioner failure
- Slight overpressure needs to be created
- Ideally, air pressure is measured in the cold aisle area and connected to air conditioners to regulate the CFM/ CMH output
- Be aware that CFM / CMH is variable in most of today's equipment
Hot Aisle Containment
- The hot aisle area is contained
- Hot air is separated from the cold air and is guided directly back to the air conditioner or outside of the building
- Cold air is flowing throughout the entire computer room
- Typically recommended when only a small area needs to be contained
- Cold air is going through the entire room
- Cold air should only go where it is required being the intake of the equipment
- The whole room is now acting as a buffer area
- Works well with in-row cooling
- Hot aisle areas can sometimes be very hot and noisy
- Review local regulations for personnel working in such environments
沒有留言:
發佈留言
任何人若留有政治言論,個別使用者將會被隔離這個網誌,留言系統或將會被限制,甚至關閉