Data Centre Cooling —— 30% of the total power consumption of a data centre.
Recommended temperature —— 18 - 27 °C 要監測回風溫度和進風溫度的溫度差
Recommended humidity ——
- Low-end moisture: -9 °C Dew Point
- 18 °C => 15% RH
- 27 °C => 9% RH
- High-end moisture: 60% RH and 15 °C Dew Point
- 23 °C => 61% RH
- 27 °C => 48% RH
- Too Low -> risk of electrostatic discharge
- Too High -> risk of corrosion
當相對濕度過高時,會發生水的凝結,導致硬件腐蝕和早期的系統和部件故障。如果相對濕度太低,機櫃設備就容易受到靜電放電的影響,從而導致敏感元件的損壞。在監測數據中心的相對濕度時,建議在相對濕度為40%和60%時發出預警警報,在相對濕度為30%和70%時發出關鍵警報。重要的是,相對濕度與當前的溫度直接相關,所以同時監測溫度和濕度是至關重要的。
Cooling capacity:
- Ton / BTU / Watt / Horsepower
- 1 ton = 12,000 BTUs = 3.516 kWh
- 1 BTU = 0.000293 kWh = 0.0000833 ton
- 1 kWh = 0.283 tons = 3,412 BTUs
- 1 Horsepower = 746 watt
冷氣機的基本制冷循環原理 —— 4 main components:
壓縮過程
- The compressor keeps the refrigerant flowing through the system at specific flow rates and pressure
- 從蒸發器即室內機出來的低溫低壓的制冷劑氣體,壓縮機將這部氣體壓縮為高溫高壓的氣體,形如一個水泵一樣。
冷凝過程
- The condenser rejects heat to the outdoor Compressor
- 高溫高壓制冷劑氣體進入室外機的冷凝器,再經過風扇散熱,降溫冷卻並冷凝為液態。然後,制冷劑開始散熱,在夏天用冷氣機時室外機是往外吹熱風的。
節流過程
- The expansion valve controls the quantity of refrigerant flowing into the evaporator
- 在這一個過程中,冷氣機將低溫高壓制冷劑液體變為低溫低壓氣液混合狀態。
蒸發過程
- The evaporator removes heat from the air-conditioned space
- 進入室內機的蒸發器,吸收房間內空氣的熱量,室內機就會吹出冷風,一個循環結束。